《【AS澳大利亚标准】AS 36752002 Conductors—Covered overhead— For working voltages 6.3511 (12) kV up to.doc》由会员分享,可在线阅读,更多相关《【AS澳大利亚标准】AS 36752002 Conductors—Covered overhead— For working voltages 6.3511 (12) kV up to.doc(41页珍藏版)》请在三一办公上搜索。

1、AS/NZS 3675:2002Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 2007AS/NZS 3675Australian/New Zealand StandardConductorsCovered overhead For working voltages6.35/11 (12) kV up to and including19/33 (36) kVAccessed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 2007 AS/NZS 3675:2002 This Joint Austra

2、lian/New Zealand Standard was prepared by Joint Technical Committee EL-003, Electric Wires and Cables. It was approved on behalf of the Council of Standards Australia on 7 May 2002 and on behalf of the Council of Standards New Zealand on 9 May 2002. It was published on 30 May 2002.The following are

3、represented on Committee EL-003:Australasian Railway AssociationAustralian Electrical and Electronic Manufacturers AssociationAustralian Industry GroupCanterbury Manufacturers Association New ZealandDepartment of Defence (Australia)Department of Mineral Resources, N.S.W.Electrical Contractors Associ

4、ation of New ZealandElectrical Regulatory Authorities CouncilElectricity Supply Association of AustraliaInstitution of Engineers, AustraliaMinistry of Economic Development (New Zealand)National Electrical and Communications AssociationKeeping Standards up-to-dateStandards are living documents which

5、reflect progress in science, technology and systems. To maintain their currency, all Standards are periodically reviewed, and new editions are published. Between editions, amendments may be issued. Standards may also be withdrawn. It is important that readers assure themselves they are using a curre

6、nt Standard, which should include any amendments which may have been published since the Standard was purchased.Detailed information about joint Australian/New Zealand Standards can be found by visiting the Standards Australia web site at .au or Standards New Zealand web site at www.standards.co.nz

7、and looking up the relevant Standard in the on-line catalogue.Alternatively, both organizations publish an annual printed Catalogue with full details of all current Standards. For more frequent listings or notification of revisions, amendments and withdrawals, Standards Australia and Standards New Z

8、ealand offer a number of update options. For information about these services, users should contact their respective national Standards organization.We also welcome suggestions for improvement in our Standards, and especially encourage readers to notify us immediately of any apparent inaccuracies or

9、 ambiguities. Please address your comments to the Chief Executive of either Standards Australia International or Standards New Zealand at the address shown on the back cover.This Standard was issued in draft form for comment as DR 00391.AS/NZS 3675:2002Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02

10、 Apr 2007Australian/New Zealand StandardConductorsCovered overhead For working voltages6.35/11 (12) kV up to and including19/33 (36) kVOriginated as AS 36751993.Jointly revised and redesignated AS/NZS 3675:2002.COPYRIGHT Standards Australia/Standards New ZealandAll rights are reserved. No part of th

11、is work may be reproduced or copied in any form or by any means, electronic or mechanical, including photocopying, without the written permission of the publisher.Jointly published by Standards Australia International Ltd, GPO Box 5420, Sydney, NSW 2001 and Standards New Zealand, Private Bag 2439, W

12、ellington 6020ISBN 0 7337 4547 4Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 2007PREFACEThis Standard was prepared by the Joint Standards Australia/Standards New Zealand Committee EL-003, Electric Wires and Cables, to supersede AS 36751993 and NZS/AS 36751993, Conductors Covered overhead For

13、working voltages 6.35/11 up to and including 19/33 kV.The objective of this Standard is to provide the construction, dimensions and test requirements for overhead covered conductors intended for power distribution, operating at voltages 6.35/11 (12) kV up to and including 19/33 (36) kV. Lines constr

14、ucted with covered conductors are an alternative to overhead bare conductor construction and aerial bundled cables.A rationalized range of stranded circular aluminium alloy conductors only are specified in this Standard.This Standard differs from the previous edition in the following significant way

15、s:(a)The Standard has been published as a Joint Australian/New Zealand Standard.(b)The requirements of the covering materials have been referred to AS/NZS 3808. (c)The 20 mm2 conductor size in the CC type has been deleted.(d)A 40 mm2 conductor size in the CCT type has been added.The terms normative

16、and informative have been used in this Standard to define the application of the appendix to which they apply. A normative appendix is an integral part of a Standard, whereas an informative appendix is only for information and guidance.9AS/NZS 3675:2002Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02

17、 Apr 2007CONTENTSPageSECTION 1 SCOPE AND GENERAL1.1SCOPE. 41.2REFERENCED DOCUMENTS. 41.3DEFINITIONS. 51.4VOLTAGE DESIGNATION . 51.5MAXIMUM CONDUCTOR TEMPERATURE . 6SECTION 2 CONSTRUCTION2.1CONDUCTORS . 72.2COVERING. 72.3WATER BLOCKING . 72.4IDENTIFICATION. 82.5PREPARATION FOR DELIVERY . 82.6MARKING

18、OF DRUMS . 8SECTION 3 TESTS3.1ROUTINE TESTS . 113.2SAMPLE TESTS . 113.3TYPE TESTS. 11APPENDICESAAPPLICATION GUIDE . 13BPURCHASING GUIDELINES . 14CINTERSTRAND CONDUCTIVITY TEST . 15DSTATIC WATER BLOCKING TEST . 16EDYNAMIC WATER BLOCKING TEST . 19FSTRIPPING TEST . 21GADHESION TEST. 23HUV WEATHERING TE

19、ST . 25IDRIPPING TEST . 27JA GUIDE TO SELECTION OF COVERED CONDUCTORS . 29Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 2007STANDARDS AUSTRALIA/STANDARDS NEW ZEALANDAustralian/New Zealand StandardConductorsCovered overhead For working voltages6.35/11 (12) kV up to and including19/33 (36) kVS E

20、 C T I O N1S C O P EA N DG E N E R A L1.1 SCOPEThis Standard specifies the construction, dimensions and test requirements for water blockedcoveredconductors,suitableforoverheadlinesforworkingvoltages6.35/11 (12) kV up to and including 19/33 (36) kV, 50 Hz a.c.NOTES:1An application guide is provided

21、in Appendix A.2Guidelines on information that should be supplied with enquiries or orders are provided inAppendix B.1.2 REFERENCED DOCUMENTSThe following documents are referred to in this Standard: AS1531ConductorsBare overheadAluminium and aluminium alloy3983Metal drums for insulated electric cable

22、s and bare conductorsAS/NZS1660Test methods for electric cables, cords and conductors1660.2.1Method 2.1: Insulation, extruded semi-conductive screens and non-metallic sheathsMethods for general application1660.2.4Method 2.4: Insulation, extruded semi-conductive screens and non-metallic sheathsMethod

23、s specific to polyethylene and polypropylene materials1660.3Method 3:Electrical tests2857Timber drums for insulated electric cables and bare conductors3008Electrical installationsSelection of cables3008.1Part 1:Cables for alternating voltages up to and including 0.6/1 kV3808Insulating and sheathing

24、materials for electric cablesIEC60287Electric cablesCalculation of the current ratingASTMG155Standard practice for operating xenon arc light apparatus for exposure of non-metallic materialsESAAHB C(b)1Guidelines for design and maintenance of overhead distribution and transmission linesCOPYRIGHTAcces

25、sed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 20071.3 DEFINITIONSFor the purpose of this Standard, the relevant definitions given in the referenced Standards and those below apply:1.3.1 ConductorThat portion of covered conductor which has the specific function of carrying current.1.3.2 Covered cond

26、uctorA conductor around which is applied a specified thickness of insulating material. The types in this Standard are:(a)CCA covered conductor having a 2.0 mm thickness of covering for use on all working voltages up to and including 19/33 (36) kV.(b)CCTA covered conductor which has a specified thick

27、ness of covering for each of the nominated working voltages.1.3.3 CoveringInsulating material of a specified thickness excluding any water blocking compound.1.3.4 Maximum continuous conductor temperatureThe maximum temperature at which the conductor can be operated continuously. It is the temperatur

28、e resulting from the combined effect of all contributing thermal conditions.1.3.5 Routine testsTests made by the manufacturer on each manufactured length of covered conductor to check that each length meets the specified requirements.1.3.6 Sample testsTests made by the manufacturer on samples of cov

29、ered conductor, or components taken from a completed covered conductor, at a specified frequency, so as to verify that the finished product meets the specified requirements.1.3.7 Type testsTests made before supplying, on a general commercial basis, a type of covered conductor covered by this Standar

30、d, in order to demonstrate satisfactory performance characteristics to meet the intended application. These tests are of such a nature that, after they have been made, they need not be repeated unless changes are made in the covered conductor materials or design or manufacturing process, which might

31、 change the performance characteristics. Where changes are made, repeat tests shall be limited to those needed to prove compliance with this Standard.1.3.8 Ungreased conductorA conductor which is dry and free from grease, other than a light residue of wire drawing lubricant that may be on the wires.

32、1.4 VOLTAGE DESIGNATIONIndication of the rated voltages shall be expressed in the form Uo/U (Um)whereUois the r.m.s. power frequency voltage to earth of the supply system, for which the covered conductor is designed.Accessed by UNIVERSITY OF SOUTH AUSTRALIA on 02 Apr 2007Uis the r.m.s. power frequen

33、cy voltage between phases of the supply system, for which the covered conductor is designed.Umis the maximum r.m.s. power frequency voltage between any two phases of the supply system for which covered conductors and accessories are designed. It is the highest voltage that can be sustained under nor

34、mal operating conditions at any time and at any point in a system. It excludes temporary voltage variations due to fault conditions and sudden disconnection of large loads.1.5 MAXIMUM CONDUCTOR TEMPERATUREThe temperature of the conductor shall not exceed the following values:(a)Normal operation. 80C

35、 (b)Emergency operation . 100C (c)Short-circuit operation (5 s max.) . 210CNOTE: The maximum temperatures given are based upon the properties of the conductors, but inpractice they may need to be derated to take account of joints and terminations.Over the 30 year life expectancy the covered conducto

36、r should not operate at the emergency operation temperature more than three times in any 12 successive months nor for any single period exceeding 100 h.At the emergency operating temperature, the cable covering may suffer deformation due to external forces applied at supports.Accessed by UNIVERSITY

37、OF SOUTH AUSTRALIA on 02 Apr 2007S E C T I O N2C O N S T R U C T I O N2.1 CONDUCTORS2.1.1 MaterialsConductors shall all be ungreased aluminium alloy, in accordance with AS 1531, of the sizes specified in Tables 2.1 or 2.2 herein.For conductor water blocking requirements see Clause 2.3.2.2 COVERING2.

38、2.1 Covered conductors (CC)2.2.1.1 MaterialThe conductors shall be covered with ultraviolet (UV) stabilized X-90, complying with the requirements of AS/NZS 3808.If the UV stabilization is achieved by the addition of a minimum of 2% carbon black then the covering shall comply with the requirements for unprotected X-90 insul