1、DriveWindow 2,DriveWare,Introduction,DriveWindow is Windows Application for commissioning and maintaining ACS600,ACS800,ACS6000,ACS1000 and DCS600.Operating system Windows NT,Windows 2000,or Windows XP,FunctionsControl operations(start,stop,references,etc.)Monitoring signals in numerical and graphic
2、al formatParameters(changing values)Datalogger(controls,display)Fault Logger(display faults,controls)Back-up&Restore(complete software back-up)All functions over network(control,monitoring,etc.),Required DriveWindow hardware:ISA card,orPCMCIA-card(PCMCIA-slot or PCI-slot with PCI/PCMCIA adapter)Netw
3、ork adapter when using remote connectionDDCS cabling,Connection,.,8 7 6 0,NDBU-95/85,NISA-03(ISA),DDCS-protocol 1 Mbit/s,OR,GOFmax 1000m(NOCR-01 isrequired)HCSmax 200 mORPOFmax 30m,.,GOF=Glass Optic FibreHCS=Hard Clad Silica FibrePOF=Plastic Optical Fibre,Connection alternatives:1.Direct connection(
4、point-to point)between the PC and the drive(the most common manner)2.Through the distributor,DriveWindow-link(sectional drives).An individual address to be set by parameter 70.02 or 70.15 for every drive in the link.3.Ring.Drives can be connected in a ring.An individual address to be set by paramete
5、r 70.02 or 70.15 for every drive in the link.Note!all the drives in the ring should have power supply on all the time.Otherwise the ring will break.Note!Do not use address one(1)if several drives are in a network(ring or connected together with the distributors).The first(1.)address are meant for sp
6、arepart use.,CH 3,CH 3,CH 3,Optical distributor 9 channels,CH 3,NDPA-02(PCMCIA)+NDPC-02(5Mb)or NDPC-12(10Mb),MSTR,8 7 6 0,NDBU-95/85,MSTR,CH 3,CH 3,PCMCIA-adapter(PCI)+NDPA-02(PCMCIA)+NDPC-02(5Mb)or NDPC-12(10Mb),OR,HCSmax 200 mORPOFmax 30m,OR,Double-clickthe program icon,Getting start,1.,Select OK,
7、Most of the operationscan be done only when the drive is in REMOTE-control(Not the local control with the DriveWindow),User Interface,OFF-LINE or COMM.BREAK,NOT RUNNING,RUNNING(forward),FAULT,WARNING,DRIVE STATUS,BROWSE TREEPANE,TREND DISPLAY PANE,TREND SETTINGSPANE,ITEM LIST PANE,Size of the window
8、 partscan be changes,Open Browse Tree by Double-clicking the motor,Toolbar,Status refresh off/on,STANDARD(general),MONITOR,LOGGER,Cut,Copy,Delete,Zoom In,Zoom Out,Reset Zoom,Add Item,Lock/unlock Item into theDesktop,Update items,Select On-/off-line for items,Change value,Add/removeMonitor Items,Star
9、tMonitoring,StopMonitoring,PauseMonitoring,ClearMonitor,StopDatalogger,TrigDatalogger,ClearDriveDatalogger,ClearDataloggerGraph,StartDatalogger,Upload Datalogger,Add/RemoveLoggerItems,Drive Panel Toolbar,Stop,Take/Release Control(Local/Remote),Name and address of the selected drive,Setting of parame
10、ters,Click+symbol by mouse,Double-click group by mouse,Double-click item by mouse,+,Select or type new value for the parameter.Select OK,4,NOTE!If the drive running when a parameter group is expanded(opened into the Item List Pane),editing of the some parameters are not possible.This READ ONLY-statu
11、s remains afterward even the drive have been stopped.Solution:1.Disconnect Server-command from the Network-menu2.Network Servers-command from the Network-menu,Actual values,Click+symbol with mouse,Click the group with mouse,Click item with mouse,+,Select ACTIVATE/DEACTIVATE ITEMSfrom the Toolbar,NOT
12、E!If desired values are located in a different groupsuse LOCK/UNLOCK from the Toolbar to keep them in the Item List Pane,Graph preferences,Scaling method.,Change scalings by double-clicking a row.Scale setting depend on selelected Scaling Method.Values at 100 and 0Coefficient and Offset(display=coef
13、f*Act.+offset),Selected item can be removed from the Monitor by the DEL-key of the keyboard or-button from the Toolbar,Monitor:Select items,Click item by mouse,Select ADD/REMOVE MONITORED ITEMSfrom Toolbar,Selected item shown in the monitor and it is markedin the signal list,3,Monitor:Settings and s
14、caling,Scalings;depend on selected Scaling Method,see previous slide.Display=Cofficient*ACT value+offset ORDisplay=100%with full signal range,Size of the buffer in seconds“Size of the history behind the screen”,Sampling interval in ms“Size of the history”,Monitor mode:Normal or Fast Within the Norma
15、l mode min.sampling interval is 10mswithin Fast-mode it is 1ms,Set y-axis minimum and y-axis maximum,=You can set at any time.,=You can set only when monitoring is cleared.,=You can set when monitoring is stopped or paused,Length of the screen in seconds Change the length by double-click it,if it is
16、 necessary,Monitor:Operating,1.Add/remove monitored items2.Start or continue monitoring3.Stop monitoring4.Pause monitoring5.Clear monitor,Select START,Select STOP or PAUSE,Print out,Export data in numerical form e.g.into the Excel-program,Copy Graph into the Clipboard,Open a saved graph file in the
17、offline mode,Save the graphs to the file,Graph file comment,Graph Preferences:scaling method,how graphs are shown etc.,Workspace,Change the preferences for workspace save&restore,DriveWindowWorkspace,Open a saved workspace file in the online or offline mode,Save the workspace to the file,Fault logge
18、r,It is possible clear the selected driveFAULT LOGGER,Select the row(s)and update items,Click theFault Logger,Fault or Warning messages,Desktop preferences:From Cache:values are pick up from the OPC Server cacheFrom Device=“all actual values are pick up from the drive with separate commands”.It is n
19、ot on-line and causes less load for the communication than other selections.Thus the contents of the fault logger are not updated even it is open on the desktop.By double-clicking with mouse the fault logger icon or by the Update Items-button the contents will be updated.PUT ON-LINE=is full time and
20、 real on-line connection.This is applicable also with the parameters and signals.But this causes more load for the communication,which should take into consideration in case by case.See more information from DriveWindow ONLINE HELP,Save parameter file to the PC,Select the drive,Give a filename and l
21、ocate the file into a hard disk/directory,2,Give a comment and select OK,Command is disabled(grayed)while the LOCAL CONTROL.Use Take/Release Control,NOTE!If the drive running when a parameter set is save to the PC,editing of the some parameters are not possible in the OFFLINE.This READ ONLY-status r
22、emains in the parameter file.For the backup purpose create always the FULL BACKUP of the control board or control unit(NAMC-xx,RMIO-xx,NDCU-xx),see slide 18.,Download parameters into the drive,Open the file,Select the drive(Remote Control),Select DOWNLOAD,Different sw-versionsSw conflict!,Select typ
23、e 10.98Set parameters into the group 99 manually afterwards,Are you sure?,Pick up file,NOTE!In case of the ACS800,check after download the parameters from the group 83 and 84(If Adaptive Program is in use),Create full Backup of the motor control board,Select Save As.,Open the new“backup FOLDER”(The
24、drive should be in REMOTE CONTROL=not the control from the DriveWindow),Backup,Select the drive,Give a filename,Last action:Close your folderFILE-menu-SYSTEM SOFTWARE-CLOSE,Note!For safety reasons you cannot restore any drivewhile control of some drive is taken with DW=LOCAL control.The command in t
25、he menu is disabled(grayed).,Restore Backup file into the motor control board,Are you sure?,Open the backup file,Select the System Software/Restore,Select the drive where you want RESTORE(=backup file),Select the right BACKUP(-file)for the RESTORE(The backup foldermay contain more than backup).,Dont
26、 do any operations with drive or PC during Restoring,DATALOGGER:Overview,-Datalogger is data recorder.Its locating in the drive and control of it are done by the DriveWindow-Number of dataloggers are two(2)(with the NAMC-03/-11 in ACS 600 one(1)datalogger is available)-Total number of samples(n)are
27、1024(ACS 600,ACS 800)-Number of the channels are four(4)(ACS 600,ACS 800)-If four(4)channels were defined,samples per channel are 256-Triggering conditions are defined by user(fault,level of a measured signal,warning etc.),Channel 1,e.g.ActualSpeed,Channel 2,e.g.ActualFreq.,Channel 3,e.g.ActualCurre
28、nt,Channel 4,e.g.ActualTorque,n,LOCATION OF THE DATALOGGER,CONTROL OF THE DATALOGGER,DriveWindow,You can set x-axis length of the monitor or a datalogger at any time.X-axis length of a datalogger can also change automatically when the datalogger is uploaded.Note!If a datalogger has never been upload
29、ed,DriveWindow does not know for sure the size of a datalogger channel buffer.Thus DriveWindow does not do any checking about the x-axis length,until it knows more about the datalogger.When size of the datalogger channel buffer is known,DriveWindow does not accept improper setting of x-axis length.,
30、Interval,where you can change the logging interval of the current datalogger.,Pre-Trig(ms),where you can change the number of values kept in the current datalogger before the triggering event.The value is given and shown as time,but the datalogger actually uses a count.,Trig Hysteresis,where you can
31、 change the triggering level hysteresis,which is used in triggering the current datalogger.,Trig Level,where you can change the triggering level,which is used in triggering the current datalogger.,Trig Conditions(fault,warning,level etc).,Trig Variable,where you can change OPC address of the variabl
32、e,which is used in triggering the current datalogger.,Status shows the state of the datalogger.Double-clicking toggles it on-line/off-line.Trigged By shows the triggering reason,Scale channel 1;Two scaling methods available.Same method selected for Monitoring and Datalogger from FILE-menu:Graph/Pref
33、erences.Change the scale by double-click channel number.,DATALOGGER:Settings,Select the new signal by the mouse,Add the signal into the datalogger.Repeat points 2 and 3 with all four channels.Note!You cannot specify used channel.DriveWindow defined used channel automatically,Start datalogger,When FILLED,upload data,DATALOGGER:Example,Delete existing signals from Datalogger one by one,Make your datalogger settings.Scalings,like X-axis length can be done after the uploading,