1、Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSIBRITISH STANDARD BS EN61558-2-19:2001IEC 61558-2-19:2000Safety of power transformers, power supply units and similar devices Part 2-19: Particular requirements for
2、perturbation attenuation transformersThe European Standard EN 61558-2-19:2001 has the status of aBritish StandardICS 29.180NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBS EN 61558-2-19:2001National forewordThis British Standard is the official English language version ofEN 6
3、1558-2-19:2001. It is identical with IEC 61558-2-19:2000.The UK participation in its preparation was entrusted to Technical CommitteePEL/96, Small transformers, which has the responsibility to:aid enquirers to understand the text;present to the responsible international/European committee any enquir
4、ies on the interpretation, or proposals for change, and keep the UK interests informed;monitor related international and European developments and promulgate them in the UK.A list of organizations represented on this committee can be obtained on request to its secretary.From 1 January 1997, all IEC
5、publications have the number 60000 added to the old number. For instance, IEC 27-1 has been renumbered as IEC 60027-1. For a period of time during the change over from one numbering system to the other, publications may contain identifiers from both systems.Cross-referencesAttention is drawn to the
6、fact that CEN and CENELEC Standards normally include an annex which lists normative references to international publications with their corresponding European publications. The British Standards which implement these international or European publications may be found in the BSI Standards Catalogue
7、under the section entitled “International Standards Correspondence Index”, or by using the “Find” facility of the BSI Standards Electronic Catalogue.A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct
8、 application.Compliance with a British Standard does not of itself confer immunity from legal obligations.Summary of pagesThis document comprises a front cover, an inside front cover, the EN title page,pages 2 to 14, an inside back cover and a back cover.The BSI copyright date displayed in this docu
9、ment indicates when the document was last issued.Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSIThis British Standard, having been prepared under the direction of the Electrotechnical Sector Committee, was publi
10、shed under the authority of the Standards Committee and comes into effect on15 June 2001 BSI 06-2001ISBN 0 580 37514 5Amd. No.DateCommentsAmendments issued since publicationEUROPEAN STANDARDEN 61558-2-19NORME EUROPENNEEUROPISCHE NORMMarch 2001ICS 29.180English versionSafety of power transformers, po
11、wer supply units and similar devicesPart 2-19: Particular requirementsfor perturbation attenuation transformers(IEC 61558-2-19:2000)Scurit des transformateurs, blocs dalimentation et dispositifs analogues Partie 2-19: Rgles particulirespour les transformateurs dattnuation de perturbations(CEI 61558-
12、2-19:2000)Sicherheit von Transformatoren, Netzgerten und dergleichenTeil 2-19: Besondere Anforderungenan Strminderungs-Transformatoren(IEC 61558-2-19:2000)Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSIThis Euro
13、pean Standard was approved by CENELEC on 2001-01-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.Up-to-date lists and bibliographical references
14、 concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member
15、into its own language and notified to the Central Secretariat has the same status as the official versions.CENELEC m embers are the national electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, N
16、orway, Portugal, Spain, Sweden, Switzerland and United Kingdom.CENELECEuropean Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische NormungCentral Secretariat: rue de Stassart 35, B - 1050 Brussels 2001 CENELEC - All
17、rights of exploitation in any form and by any means reserved worldwide for CENELEC members.Ref. No. EN 61558-2-19:2001 EPage 13EN 61558219:2001Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSIForewordThe text of d
18、ocument 96/147/FDIS, future edition 1 of IEC 61558-2-19, prepared by IEC TC 96, Small power transformers, reactors and power supply units: Safety requirements, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 61558-2-19 on 2001-01-01.The following dates were fixed: la
19、test date by which the EN has to be implemented at national level by publication of an identicalnational standard or by endorsement(dop)2001-10-01 latest date by which the national standards conflictingwith the EN have to be withdrawn (dow)2004-01-01This part 2-19 is to be used in conjunction with E
20、N 61558-1:1997.This part 2-19 supplements or modifies the corresponding clauses of EN 61558-1. When a particular subclause of part 1 is not mentioned in this part 2-19, that subclause applies as far as is reasonable. Where this part 2-19 states addition, modification or replacement, the relevant tex
21、t of part 1 is to be adapted accordingly.In this standard, the following print types are used:- requirements: in roman type;- test specifications: in italic type;- notes: in smaller roman type.The words in bold in the text of the standard are defined in clause 3.Subclauses, tables or figures which a
22、re additional to those in part 1 are numbered starting from 101._Endorsement noticeThe text of the International Standard IEC 61558-2-19:2000 was approved by CENELEC as aEuropean Standard without any modification._Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 1
23、6:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSICONTENTSPageClause1Scope . 42Normative references . 53Definitions. 54General requirements. 55General notes on tests . 56Ratings . 57Classification . 68Marking and other information . 69Protection against accessibility to hazardous live parts . 710 Ch
24、ange of input voltage setting . 811 Output voltage and output current under load . 812 No-load output voltage . 813 Short-circuit voltage . 9 14 Heating . 915 Short circuit and overload protection . 916 Mechanical strength . 917 Protection against harmful ingress of dust, solid objects and moisture
25、. 918 Insulation resistance and dielectric strength . 919 Construction . 920 Components .1221 Internal wiring .1222 Supply connection and other external flexible cords .1223 Terminals for external conductors .1224 Provision for protective earthing .1225 Screws and connections .1226 Creepage distance
26、s, clearances and distances through insulation .1327 Resistance to heat, abnormal heat, fire and tracking.1328 Resistance to rusting.1329 Annexes .14Figure 101 Protection of the output circuit in case of short circuit . 11Table 101 Maximum disconnecting time . 11 BSI 06-2001Licensed Copy: Institute
27、Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSISAFETY OF POWER TRANSFORMERS, POWER SUPPLY UNITS AND SIMILAR DEVICES Part 2-19: Particular requirementsfor perturbation attenuation transformers1ScopeReplacement:This International Standard
28、 deals with all aspects of safety such as electrical, thermal and mechanical.This part 2-19 of IEC 61558 applies to stationary or portable, single-phase or poly-phase, air- cooled (natural or forced), independent or associated, isolating or safety isolating transformers, having a rated supply voltag
29、e not exceeding 1 000 V a.c., a rated frequency not exceeding 500 Hz, a rated output not exceeding 10 kVA. Perturbation attenuation transformers are intended to the supply of office machines and the like and have a mid-point lead out in the output circuit in order to attenuate mains borne disturbanc
30、es.In addition, double or reinforced insulation between circuits required by the installation rules or by the appliance specification is fulfilled by using this transformer.NOTE 1 Connection of an appliance via transformers of the kind referred to here does not imply that the requirements for this a
31、ppliance are allowed to be less stringent.Perturbation attenuation isolating transformers:have a no-load output voltage and a rated output voltage exceeding 50 V a.c. or 120 V ripple-free d.c. and not exceeding 500 V a.c. or 708 V ripple free d.c.; the no-load output voltage and the rated output vol
32、tage may exceed these limits in order to be in accordance with the national wiring rules or special purposes, however they shall not exceed 1 000 V a.c. or 1 415 V ripple free d.c.Perturbation attenuation safety isolating transformers:have a no-load output voltage and a rated output voltage not exce
33、eding 50 V a.c. or120 V ripple-free d.c.This standard is applicable to dry-type transformers. The windings may be encapsulated or non-encapsulated.W here an isolating transformer provides supply to two or more items of equipment, a connection of exposed-conductive-parts of such equipment is required
34、 in accordance with section 413.5 of IEC 60364-4-41.NOTE 2 For transformers filled with liquid dielectric or pulverised material, such as sand, additional requirements are under consideration.NOTE 3 Attention is drawn to the fact that:for transformers intended to be used in tropical countries, speci
35、al requirements may be necessary;in locations where special environmental conditions prevail, particular requirements may be necessary.Licensed Copy: Institute Of Technology Tallaght, Institute of Technology, Mon Jun 11 16:48:32 GMT+00:00 2007, Uncontrolled Copy, (c) BSINOTE 4 This part 2-19 does no
36、t prevent the use of other types of transformers as attenuation transformer without mid-point in the output circuit.This standard does not cover the performances of the function attenuation. This function may be obtained by different features, for example: screen or special lamination.This standard
37、also applies to transformers incorporating electronic circuits. This standard does not apply to external circuits and their components intended to be connected to the input and output terminals or socket-outlets of the transformer.2Normative referencesThis clause of part 1 is applicable.3DefinitionsThis clause of part 1 is applicable except as follows:Addition:3.101perturbation attenuation transformertransformer with a