1、豆丁网:BRITISH STANDARDRefrigerating systems and heat pumps Safety switching devices for limiting the pressure Requirements and testsThe European Standard EN 12263:1998 has the status of aBritish StandardICS 27.080; 27.200| BS EN12263:1999|NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRI

2、GHT LAWBS EN 12263:1999National forewordThis British Standard is the English language version of EN 12263:1998.The UK participation in its preparation was entrusted to Technical CommitteeRHE/18, Refrigeration safety, which has the responsibility to: aid enquirers to understand the text; present to t

3、he responsible European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK.A list of organizations represented on this committee can be obtained on request t

4、o its secretary.Cross-referencesThe British Standards which implement international or European publications referred to in this document may be found in the BSI Standards Catalogue under the section entitled International Standards Correspondence Index, or by using theFind facility of the BSI Stand

5、ards Electronic Catalogue.A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application.Compliance with a British Standard does not of itself confer immunity from legal obligations.Summary of pagesT

6、his document comprises a front cover, an inside front cover, the EN title page, pages 2 to 9 and a back cover.Amd. No.DateText affectedThis British Standard, having been prepared under the direction of the EngineeringSector Committee, was published under the authority of the Standards Committee and

7、comes into effect on 15 April 1999BSI 04-1999ISBN 0 580 29284 3Amendments issued since publicationEUROPEAN STANDARDEN 12263NORME EUROPE ENNEEUROPA ISCHE NORMNovember 1998ICS 27.080; 27.200Descriptors: cooling systems, refrigerating, heat pumps, safety devices, pressure limiters, specifications, test

8、s, testing conditions, adjustment, instructions, markingEnglish versionRefrigerating systems and heat pumps Safety switching devices for limiting the pressure Requirements and testsSyste mes de re frige ration et pompes a chaleur Dispositifs-interrupteurs de se curite limitant la pression Exigences

9、et essaisKa lteanlagen und Wa rmepumpen Sicherheitsschalteinrichtungen zurDruckbegrenzung Anforderungen und Pru fungenThis European Standard was approved by CEN on 4 March 1998.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this Eu

10、ropean Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (Englis

11、h, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.CEN members are the national standards bodies of Austria, Belgium, Czech Republi

12、c, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.CENEuropean Committee for Standardization Comite Europe en de Normalisation Europa isches Komitee fu r NormungCentral Secretariat: rue de St

13、assart 36, B-1050 Brussels1998 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN nationalMembers.Ref. No. EN 12263:1998 EPage 5EN 12263:1998BSI 04-1999ForewordThis European Standard has been prepared by Technical Committee CEN/TC 182, Refrigerating systems, safet

14、y and environmental requirements, theContentsPageSecretariat of which is held by DIN.This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 1999, and conflicting national standards shall be withdrawn

15、 atthe latest by May 1999.This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of the EUDirective 97/23/EC.For relationship with EU Directive(s), see informative annex ZA, which i

16、s an integral part of this standard.According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,

17、Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.Foreword 21Scope 32Normative references 33Definitions 34Requirements and tests 45Installation and operating instructions 76Marking 7Annex A (informative) Symbols and equivalentterms in English, French and Ge

18、rman 8Annex ZA (informative) Clauses of this EuropeanStandard addressing essential requirements orother provisions of EC Directives 91 Scope1.1 This European Standard establishes the requirements and tests applied to safety switching devices for limiting the pressure (hereafter called devices) to en

19、sure that the maximum or minimum pressure, which is caused by a pressure generator in refrigerating systems and/or heat pumps, is maintained within the limits of the refrigerating system and/or heat pump. These devices are of special construction andare equipped with mechanically operated output con

20、tacts.NOTE Devices may be wired directly into the control circuit of the compressor or may be connected through a relay or microprocessor/computer.Transducers/analogue devices are not covered by this standard.If more stringent specifications for special applications are necessary, these should be ag

21、reed between the customer and the manufacturer of the devices.1.2 Different safety and control functions can be combined in one device.1.3 This standard does not apply to devices used for control purposes.2 Normative referencesThis European Standard incorporates, by dated or undated reference, provi

22、sions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European Standard onlywhen incorporated in it by

23、 amendment or revision. For undated references, the latest edition of the publication referred to applies.EN 60529, Degrees of protection provided by enclosures(IP code).(IEC 529:1989)EN 60730-1:1995, Automatic electrical controls for household and similar use Part 1: General requirements.(IEC 730-1

24、:1993, modified)EN 60730-2-6:1995, Automatic electrical controls for household and similar use Part 2: Particular requirements for automatic electrical pressure sensing controls including mechanical requirements.(IEC 730-2-6:1991, modified)EN 60947-5-1:1991, Low-voltage switchgear and controlgear Pa

25、rt 5: Control circuit devices and switching elements Section 1: Electromechanical control circuit devices.(IEC 947-5-1:1990)EN 60068-2-6, Environmental testing Part 2: Tests Test Fc: Vibration (sinusoidal).(IEC 68-2-6:1995 + corrigendum 1995)3 DefinitionsFor the purposes of this European Standard th

26、e following definitions apply.NOTE Symbols and equivalent terms are specified in annex A.3.1safety switching device for limiting pressurepressure-actuated device that is designed to stop the operation of the pressure generatorNOTE These devices can be designed to limit the high pressure (H) or to li

27、mit the low pressure (L) to one predetermined value during abnormal operating conditions.3.1.1pressure limiterdevice which automatically resetsNOTE 1 It is called PSH for high-pressure protection and PSL for low-pressure protection (see annex A).NOTE 2 The devices automatically cut out when a set pr

28、essure limit is exceeded, and they automatically cut in again.3.1.2pressure cut-outdevice which is manually reset without the aid of a toolNOTE 1 It is called PZH for high-pressure protection and PZL for low-pressure protection (see annex A).NOTE 2 The devices automatically cut out when a set pressu

29、re limit is exceeded and are manually reset without the aid of a tool.3.1.3safety pressure cut-outdevice which is manually reset only with the aid of a toolNOTE 1 It is called PZHH for high-pressure protection and PZLLfor low-pressure protection (see annex A).NOTE 2 The devices automatically cut out

30、 when a set pressure limit is exceeded and are manually reset only with the aid of a tool.3.2cut-out pressurepressure at which the contacts in the control circuit open to stop the pressure generatorNOTE This will occur with a rising pressure for high-pressure protection and a falling pressure for lo

31、w-pressure protection.3.3cut-in pressurepressure at which the contacts in the control circuit close to start the pressure generatorNOTE This will occur with a falling pressure for high-pressure protection and a rising pressure for low-pressure protection, as well as by manual reset.3.4setting rangep

32、ressure range within which the cut-out pressure can be set3.5upper switching pressurepressure at which the device switches during pressure rise (cut-out or cut-in)3.6lower switching pressurepressure at which the device switches during pressure fall (cut-out or cut-in)3.7 differentialpressure differe

33、nce between the upper and lower switching pressureNOTE For devices with manual reset, the lower or upper switching pressure will be that at which the device is capable of being reset.3.8 driftpermanent alterations which can occur when a device has been tested under the conditions specified in this s

34、tandard3.9 deviationtemporary alterations which disappear when the device is no longer subjected to the test conditions3.10maximum declared pressure, pmaxpressure, declared by the manufacturer, to which the component or device may be subjected without reducing its performance3.11allowable temperatur

35、e rangerange between the maximum and minimum ambient temperature within which the performance of the device is not reduced4 Requirements and tests4.1 General requirements and test conditions Devices shall be so designed and constructed that in normal use they function so as to cause no danger topers

36、ons and surroundings, even in the event of anyforeseeable misuse which may occur during operation.Unless otherwise specified, all tests shall be carried out at an ambient temperature of 20 8C to 25 8C. For accuracy of measurement, the pressure applied to the device shall not change at a rate of more

37、than 10 bar/min.Three samples of each type shall undergo and pass all the described tests.However, only two are used for the burst test and the third for the test of fail-safe function of the measuring element.4.2 Mechanical requirements4.2.1 Design and enduranceThe materials used in the constructio

38、n of the devices shall be able to withstand the thermal, mechanical and chemical stresses occurring in the range of application for which the devices are provided. Corrosive effects, in particular, shall not affect the function of the devices.The design of the device shall ensure a snap-action chara

39、cteristic of the contact system.Devices with automatic reset shall have a mechanical life of at least 5 000 switching operations.Devices with manual reset shall withstand at least 500 reset operations.In addition, the devices shall withstand atleast 50 000 pressure cycles without switching.4.2.2 Dev

40、ices with manual resetThe manual reset shall be designed trip-free according to 2.3.15 of EN 60730-1:1995. The reset mechanism shall be independent of other setting mechanisms.4.3 Electrical requirements4.3.1 SafetyFor electrical safety, the following clausesof EN 60730-2-6:1995 are applicable and t

41、he manufacturer shall declare compliance thereto: clause 8: Touch protection against electric shock; clause 9: Provision for protective earthing; clause 12: Moisture and dust resistance; clause 13: Electrical strength and insulation resistance; clause 14: Heating; clause 17.2: Electrical conditions

42、for the tests; clause 19: Threaded parts and connections; clause 20: Creepage distances, clearances and distances through insulation; clause 21: Resistance to heat, fire and tracking.4.3.2 Fuse protectionThe required fuse protection against short circuit shall be indicated by the manufacturer in acc

43、ordancewith 8.3.4 of EN 60947-5-1:1991.4.4 Setting, range and accuracy4.4.1 Set-point adjustmentThe cut-out pressure shall be shown on the device, either by marking of a fixed setting or by a scale indication on adjustable devices.On adjustable devices, changes of setting shall only be possible by m

44、eans of a tool.It shall be possible to protect the devices against alteration of settings by unauthorized persons.4.4.2 Setting rangeHigh-pressure devices shall be protected against excessive set-point adjustment above the maximum set-point range. This protection shall not allow acut-out pressure higher than the maximum range value +15 % or +3 bar, whichever is the greater.4.4.3 Accuracy of settingThe